A closed loop is supposed to be closed. In practice, many of them quietly take on makeup water through a leaking valve, a failed auto-fill, a cracked coil or a weeping seal, and nobody notices until inhibitor levels collapse or corrosion shows up. The makeup meter, if there is one, is rarely read. A PTSA tracer gives you a second, independent way to catch it: the loop’s own chemistry tells you when fresh water is getting in.
This article explains how a stable PTSA reading doubles as a leak indicator, how to turn a drop in concentration into a leakage rate, and where the method stops working. It applies to chilled water, hot water and condenser loops across Malaysia.
Why PTSA Behaves Like a Leak Detector
PTSA is a colourless fluorescent dye that is not consumed by normal system demand. Once it is mixed into a closed loop, its concentration should stay flat. The only things that change it are dilution with untraced water, or loss of traced water that is replaced with untraced water.
That is the useful part. If the PTSA reading falls with no change in dosing, untraced water has entered the loop. Pyxis makes the same point in its VoluCheck guidance: if a stable reading cannot be established, check whether fresh makeup water is being added through an unknown leak.
The Direct Answer: Can PTSA Detect a Closed Loop Leak?
Yes, for leaks that bring makeup water into the loop. Dose PTSA to a stable reading, log the concentration at regular intervals, and treat a steady downward trend as makeup water entering. A closed loop holds a fixed volume, so water coming in means an equal volume is leaving somewhere, through a leak, a vent or an expansion tank overflow. PTSA does not show you where, only that water is being exchanged.
Step 1: Establish a Stable Baseline
Measure the PTSA background, dose to a target between 80 and 260 ppb, and let the loop recirculate until the reading stops moving. Allow at least 30 minutes of mixing, longer for loops with low recirculation or stagnant branches. Record this as your reference concentration and the date.
If you dose a PTSA-traced treatment product, the baseline will drift with every top-up. For a clean leak test, use a loop where PTSA is not being added routinely, or log your doses so they can be subtracted.
Step 2: Log the Reading on a Fixed Schedule
Take the same measurement at the same interval, daily for a suspect loop, weekly for routine monitoring. Use a fluorometer that reads PTSA, such as the Pyxis SP-350 (0-300 ppb), SP-380 or SP-400. Filter coloured or turbid samples through a 0.45 micron syringe filter, and use the same sample handling each time so the trend is real.
A reading that moves by a few ppb either way is noise. A reading that falls steadily in the same direction across several readings is not.
Step 3: Turn the Drop into a Leakage Rate
You need the loop volume, which the VoluCheck test gives you. Then apply a simple dilution relationship. If the loop volume is V, the starting concentration is C0 and the current concentration is C, the volume of untraced water that has entered (and an equal volume that has left) is:
Water exchanged = V x ln(C0 / C)
A worked example, with illustrative numbers: a 20,000 US gallon chilled water loop reads 100 ppb on day 0 and 90 ppb on day 7.
Water exchanged = 20,000 x ln(100 / 90) = 20,000 x 0.105 = about 2,100 US gallons over 7 days, or roughly 300 gallons per day (about 1.1 m³/day).
For small drops, the shortcut is close enough: a 10% fall in concentration means about 10% of the loop volume has been exchanged. For larger drops, use the logarithm, because each new pulse of makeup dilutes already-diluted water.
What the Pattern Tells You
The shape of the trend is diagnostic, not just the size. A steady, near-linear decline suggests a continuous leak or a stuck auto-fill valve. Sudden steps down suggest discrete events, such as a manual top-up, a flush or a one-off valve failure. A flat reading that suddenly starts falling after maintenance points to something disturbed during that work.
It also helps to compare against the makeup meter if one exists. If PTSA says 300 gallons per day were exchanged and the meter shows nothing, the water is entering through an unmetered path.
Where the Method Does Not Work
Three limits matter. First, a pure outward leak does not change the PTSA concentration, because tracer and water leave together, so you detect it through falling level or makeup demand instead. Second, deliberate makeup, blowdown and flushing also dilute the tracer, so these must be logged and excluded from the leak calculation. Third, the usual interferences apply: cationic biocides and polymers such as quaternary amines, high turbidity, heavy colour and dyed loops can all distort the PTSA reading. Dilute dyed samples with DI water and multiply by the dilution factor.
Also confirm the instrument is not the problem. A dirty sample cell reads low, which looks exactly like dilution. The SP-300/400 handhelds include a cleanliness diagnostic, so run it before concluding the loop is leaking.
Handheld Checks vs Continuous Monitoring
A handheld works well for suspect loops and periodic audits. For critical loops where a slow leak is costly, an inline fluorometer reading PTSA continuously can flag a downward trend without anyone taking a sample. Pyxis handhelds are designed to correlate directly with its inline fluorometers, so handheld results can be used to verify an installed sensor. Contact us to confirm the right inline model and range for your loop.
The Bottom Line
A stable PTSA reading is more than a volume tool. It is a baseline, and any steady fall from that baseline means makeup water is entering a loop that should be closed. With the loop volume from a VoluCheck test, you can convert that fall into gallons per day and decide whether the leak is worth chasing. For plants in Malaysia running chilled or hot water loops, it is a cheap way to catch leaks before they cost you inhibitor and equipment. To set up a PTSA leak-monitoring routine, contact info@autoflotechnology.com.
Frequently Asked Questions
Can PTSA detect a leak where water is escaping from the loop?
Not directly. Water and tracer leave together, so the concentration stays the same. Outward leaks show up as falling level or rising makeup demand. PTSA detects the case where untraced water enters and dilutes the loop.
How big a leak can PTSA detect?
That depends on loop volume, reading resolution and how long you monitor. Small leaks need a longer logging period before the downward trend rises above normal noise. Larger leaks show within days.
Do I need to know the system volume to detect a leak?
No, for detection a falling trend is enough. You need the volume to convert the drop into gallons or litres per day, which is why running a VoluCheck volume test first is useful.
Will routine makeup or blowdown give false alarms?
Yes, because any addition of untraced water dilutes the tracer. Log deliberate makeup, blowdown and flushing events, and exclude them from the leak calculation.
Which fluorometer should I use for leak monitoring?
The Pyxis SP-350 is the dedicated PTSA handheld (0-300 ppb). The SP-380 adds fluorescein and the SP-400 adds conductivity, which is useful if you want a second indicator of makeup water entering the loop. For continuous monitoring, ask us about Pyxis inline fluorometers.