Every boiler feedwater and steam condensate analyser on the market — including the Pyxis Guardian IK-2000 series — specifies that it must be installed downstream of a sample cooler. This...
Turn-key panel analysers for continuous, real-time monitoring — from data centre coolant loops to cooling towers, boiler feedwater and pump-free colorimetric chemistry. Pyxis online analysers for water treatment sites across Malaysia.
Where a controller reads a single probe, an analyser is a complete turn-key monitoring panel — smart sensors, flow control, data logging and display engineered together for one application. The Pyxis IK-1500 series panelises pH, conductivity, turbidity and glycol monitoring for AI/HPC data centre coolant distribution loops. The Guardian series covers industrial cooling water and boiler feedwater with auto-brushing chlorine sensors or modular plug-and-play smart sensors that expand over time. The IK-73X-PLUS series is a dedicated auto-brushing turbidity analyser down to 0.002 NTU resolution. And the Titronex MFA series replaces conventional peristaltic-pump wet chemistry with pump-free colorimetric cartridges for hardness, chlorine, phosphate and polymer. Every analyser here is built around Pyxis Lab smart sensor technology for accurate, low-maintenance, continuous readings.
Turn-key panel design — sensors, flow tee, data logger and display pre-engineered and factory-tested as one unit, not assembled on site
Auto-brushing and pump-free options — mechanical self-cleaning electrodes or cartridge-based colorimetry cut routine maintenance versus conventional analysers
4-20mA and RS-485 Modbus outputs — integrates directly with PLCs, BMS, DCIM or EPMS platforms already on site
Application-matched sensor sets — cooling water, boiler feedwater, data centre cooling and colorimetric chemistry each have a purpose-built panel
Panelised smart sensor monitoring for AI/HPC data centre CDU coolant loops — pH, temperature, conductivity, turbidity and glycol concentration simultaneously, with 4-20mA and RS-485 Modbus outputs for BMS/DCIM integration.
Turn-key panels for corrosion, deposition and microbiological control. IK-203X auto-brushes chlorine/pH/ORP for cooling towers; IK-2000 adds DO, sulfite, conductivity and TDS sensors for boiler feedwater — expandable without reconfiguration.
Auto-brushing inline turbidity analyzer with 0.002 NTU resolution, motorized flow regulating valve and touchscreen data logging — for drinking, cooling, process and wastewater effluent applications.
Pump-free colorimetric analyzers running directly off pressurized sample flow with sealed disposable reagent cartridges — chlorine, orthophosphate, dispersant polymer and ultra-low hardness, with less maintenance than pump-driven analyzers.
Every boiler feedwater and steam condensate analyser on the market — including the Pyxis Guardian IK-2000 series — specifies that it must be installed downstream of a sample cooler. This...
A boiler that runs on poor-quality feedwater does not announce the problem immediately. The damage accumulates quietly — inside heat transfer surfaces, in the steam distribution system, at turbine blades...
Sugar mills have relied on hourly manual condensate sampling for decades, precisely because a sugar leak into boiler condensate is expensive and dangerous to leave undetected. The problem is that...
Standard conductivity measurement is one of the most common parameters in boiler feedwater and steam condensate monitoring. It is fast, inexpensive, and gives a useful general indication of total dissolved...
Tell us the loop or process — data centre cooling, cooling tower, boiler feedwater or colorimetric chemistry — and we'll match you to the right panel.