How to Measure the Volume of a Closed Loop System Using PTSA

Most closed loop systems have no reliable volume figure. The as-built drawings are missing, the loop has been modified three times, and the number on the O&M sheet is a guess. That guess drives every inhibitor dose, every glycol top-up and every flush decision, so when it’s wrong by 30%, the loop is under-treated or you’re wasting chemical. PTSA tracer gives you a measured number in an afternoon, with no draining and no flow meters.

This article explains how the PTSA dilution method works, walks through the calculation with a worked example, and covers the conditions that throw it off. It applies equally to chilled water, hot water and condenser loops across Malaysia.

What PTSA Is and Why It Works as a Tracer

PTSA (pyrenetetrasulfonic acid) is a colourless fluorescent dye. It is chemically stable in recirculating water, is not consumed by normal system demand, and can be detected by fluorometer down to single-digit ppb. A known mass of PTSA, fully mixed into an unknown volume of water, produces a concentration that depends only on that volume.

That is the whole principle. Add a known amount of tracer, measure how much the concentration rises, and the volume follows directly. It is a dilution calculation, the same one you would do with a salt solution in a beaker.

The Direct Answer: How PTSA Gives You System Volume

To measure closed loop volume with PTSA: measure the background PTSA reading, dose a pre-weighed amount of PTSA, let the loop recirculate until the reading is stable, measure the final PTSA reading, then divide the PTSA mass added by the concentration increase. Pyxis packages this as the VoluCheck kit, which uses pre-weighed bottles so that one bottle raises 1,000, 10,000 or 100,000 US gallons by 100 ppb, depending on the kit.

What You Need

Three things: a fluorometer that reads PTSA, a set of pre-weighed PTSA bottles, and a way to filter dirty samples. The Pyxis VoluCheck kit supplies the bottles, a calculation sheet and 0.45 micron syringe filters. For the fluorometer, the SP-350 (0-300 ppb PTSA, part 50206) is the dedicated unit. The SP-380 (PTSA plus fluorescein) and SP-400 (PTSA plus conductivity) also measure PTSA residual.

Pick the kit by estimated loop size:

  • VoluCheck 1K: 10 bottles of 2 oz, for 1,000 to 10,000 US gallons
  • VoluCheck 10K: 10 bottles of 4 oz, for 10,000 to 100,000 US gallons
  • VoluCheck 100K: 4 bottles of 16 oz, for 100,000 to 400,000 US gallons

Above 400,000 gallons, you need additional 100K kits.

Step-by-Step Procedure

First, fill the fluorometer sample cell with system water and record the PTSA background in ppb. If the water is heavily coloured or turbid, pass it through the 0.45 micron syringe filter first. A background reading is essential: any PTSA already in the loop would otherwise be counted as added tracer.

Second, make a rough estimate of the loop volume and choose the matching kit. An estimate within a factor of two is enough.

Third, add one full bottle to the system. Let the loop recirculate and mix for 30 minutes. If the recirculation rate is low or the loop has many stagnant branches, allow longer.

Fourth, measure the PTSA again. The ideal target is 80 to 260 ppb. If you are below that, add a second full bottle and let it mix. Record the total ounces added and the final reading.

The Calculation

The volume formula depends on the kit, because each uses a different bottle strength:

  • 1K kit: Volume (US gal) = (ounces added x 50,000) / (final ppb – background ppb)
  • 10K kit: Volume (US gal) = (ounces added x 250,000) / (final ppb – background ppb)
  • 100K kit: Volume (US gal) = (ounces added x 625,000) / (final ppb – background ppb)

A worked example, with illustrative numbers: a chilled water loop is estimated at 15,000 to 30,000 gallons, so you choose the 10K kit. The background reads 2 ppb. You add one 4 oz bottle, mix for 30 minutes, and the final reading is 52 ppb.

Volume = (4 x 250,000) / (52 – 2) = 1,000,000 / 50 = 20,000 US gallons, or about 75.7 m³.

As a sanity check, the kit is designed so that one bottle in exactly 10,000 gallons gives a 100 ppb rise. A 50 ppb rise means roughly double that volume, which matches the answer.

Conditions That Throw the Result Off

PTSA is robust, but a closed loop has chemistry that can interfere. These are the ones that matter:

  • High nitrite or turbidity: Closed loops dosed above 500 ppm nitrite, or carrying more than 100 NTU suspended solids, should be flushed first, until nitrite is below 100 ppm or turbidity below 40 NTU.
  • Existing PTSA-traced product: You can still run the test if the baseline is below 140 ppb. Above that, flush first.
  • Cationic chemistry: The method is not suitable for systems treated with quaternary amines or other cationic biocides and polymers such as Bellacide 355.
  • Colour and dye: Colour and turbidity attenuate the light and read low. Dyed loops can give negative interference. Dilute the sample with DI water, then multiply the reading by the dilution factor (10 parts DI to 1 part sample means multiply by 10).
  • Temperature: The method works for chilled and hot water systems below 200°F (93°C). Free chlorine up to 2 ppm does not affect the reading.

Reading the Mixing Behaviour

The reading itself tells you about the loop. PTSA is not consumed by normal system demand, so if you cannot get a stable reading within 6 hours, suspect fresh makeup water entering through an unknown leak. If the reading creeps slowly toward a plateau, the loop probably has large stagnant sections such as dead-legs or isolated branches. Both findings are useful on their own, and both are common in older loops in Malaysia where modifications have gone undocumented.

The Bottom Line

PTSA turns a guessed system volume into a measured one with a single dose and a fluorometer reading. For any closed loop in Malaysia where inhibitor dosing, glycol concentration or flush planning depends on knowing the real volume, it is the fastest and cheapest way to get the number. To discuss a VoluCheck kit and a matching Pyxis fluorometer for your plant, contact info@autoflotechnology.com.

Frequently Asked Questions

How accurate is PTSA volume measurement in a closed loop?
Accuracy depends on complete mixing and a clean background reading. With a stable plateau reading and no interfering chemistry, the dilution calculation is a direct result of the ppb increase. Results degrade if the loop is poorly mixed, has makeup leaking in, or if the final reading is outside the 80 to 260 ppb target range.

How long does the test take?
Mixing takes at least 30 minutes after dosing, longer for loops with low recirculation or stagnant branches. The whole test, including background reading, dosing, mixing and final reading, is usually done within a few hours.

Can I use PTSA if my closed loop is treated with nitrite?
Yes, up to a limit. Above 500 ppm nitrite, flush the loop until nitrite falls below 100 ppm before testing, because high nitrite interferes with the PTSA measurement.

Does the method work in hot water loops?
Yes. It is suitable for chilled and hot water systems below 200°F (93°C). The handheld fluorometer sample temperature range is 40 to 150°F (4 to 41°C), so hot samples must be cooled before measurement.

Which fluorometer should I use for the PTSA reading?
The Pyxis SP-350 is the dedicated PTSA handheld (0-300 ppb). The SP-380 adds fluorescein and the SP-400 adds conductivity, so either is a good choice if you also want those readings. All three compensate for colour and turbidity, and need no sample cuvette.